[1]刘宇豪,李江涛,冯 欣,等.220 kV电缆中间接头操作过电压及抑制措施研究[J].电瓷避雷器,2020,(03):146-152.[doi:10.16188/j.isa.1003-8337.2020.03.024]
 LIU Yuhao,LI Jiangtao,FENG Xin,et al.Analysis on Switching Overvoltage and Suppression Method of Cable Joint in 220 kV Cable Line[J].,2020,(03):146-152.[doi:10.16188/j.isa.1003-8337.2020.03.024]
点击复制

220 kV电缆中间接头操作过电压及抑制措施研究()
分享到:

《电瓷避雷器》[ISSN:1006-6977/CN:61-1281/TN]

卷:
期数:
2020年03期
页码:
146-152
栏目:
避雷器
出版日期:
2020-06-25

文章信息/Info

Title:
Analysis on Switching Overvoltage and Suppression Method of Cable Joint in 220 kV Cable Line
作者:
刘宇豪1 李江涛1 冯 欣1 李擎宇1 惠宝军2 张逸凡2
(1.西安交通大学,西安 710049; 2.南方电网科学研究院有限责任公司,广州 510063)
Author(s):
LIU Yuhao1 LI Jiangtao1 FENG Xin1 LI Qingyu1 HUI Baojun2 ZHANG Yifan2
(1.Xi'an Jiaotong University,Xi'an 710049,China,2.Electric Power Research Institute, China Southern Power Grid Co., Ltd., Guangzhou 510063, China)
关键词:
电缆线路 电缆接头 ATP-EMTP 操作过电压 抑制措施
Keywords:
cable line cable joint ATP-EMTP switching overvoltage suppression method
DOI:
10.16188/j.isa.1003-8337.2020.03.024
摘要:
电缆线路合闸时发生的电缆接头击穿事故时有发生,而此前电缆系统过电压仿真中均将电缆接头忽视。为此针对某220 kV电缆线路的中间接头结构,建立接头等效阻抗模型,并在暂态仿真软件ATP-EMTP中搭建考虑电缆中间接头的220 kV高压电缆系统仿真模型,仿真计算电缆中间接头的线芯与金属护层上承受的操作过电压,并研究母线不同出线数以及电缆线芯残余电荷等影响因素对电缆接头操作过电压的影响。此外还分析了电缆接头操作过电压的抑制措施。研究结果对电缆接头的故障分析、电缆绝缘配合的参数设计提供参考。
Abstract:
Disastrous breakdown accidents of cable joints happen frequently, when the closing operation of the switches is taken. However, the cable joints are often ignored in the simulation of overvoltage of cable system. In this case, based on the structure ofthe 220 kV cable joint, the equivalent impedance model is established in the paper. Impedance parameters of the cable joint are obtained by the way of measurement, and the simulation model of the 220 kV high voltage cable system considering the cable joint is built in the transient simulation softwareATP-EMTP. The simulation of switching overvoltage on the cable core and metal sheath of cable joint is conducted, and impacts on switching overvoltage of cable joints by influence factors including different number of outlets from buses and residual charges of cable core are analyzed. In addition, the analysis on suppression method of switching overvoltage of cable joint is made. Results give a reference to breakdown analysis of cable joints and parameter design of cable insulation co-ordination.

参考文献/References:

[1] 姜芸,闵红,罗俊华,李文杰,夏荣.220 kV电缆接头半导电尖端缺陷的局部放电试验[J].高电压技术,2010, 36(11):2657-2661.
JIANG Yun, MIN Hong, LUO Junhua, LI Wenjie, XIA Rong. Partial discharge pattern of semi-conductor layer tip defect in 220 kV cable joint[J]. High Voltage Engineering, 2010, 36(11): 2657-2661.
[2] 尚康良,曹均正,赵志斌,韩正一,马丽斌,李文鹏.320 kV XLPE高压直流电缆接头附件仿真分析和结构优化设计[J].中国电机工程学报,2016, 36(7):2018-2024.
SHANG Kangliang, CAO Junzheng, ZHAO Zhibin, HAN Zhengyi, MA Libin, LI Wenpeng. Simulation analysis and design optimization of 320 kV HVDC cable joint[J]. Proceedings of the CSEE, 2016, 36(7): 2018-2024.
[3] 陈羽中,谢忠巍.冷缩型电力电缆附件的技术与应用[J].绝缘材料,2004, 37(6):60-63.
CHEN Yuzhong, XIE Zhongwei. The technique & application of cold-shrinkable cable accessories[J]. Insulating Materials, 2004, 37(6): 60-63.
[4] 南方电网高压电缆附件运行及故障调研报告[R].广州:南方电网科学研究院,2017.
[5] 牛涛,许文超,钱康,施超,车尉尉.220 kV电缆线路过电压计算与分析[J].电工电气,2016(9):33-37.
NIU Tao, XU Wenchao, QIAN Kang, SHI Chao, CHE Weiwei. Calculation and analysis of 220 kV cable line overvoltage[J]. Electrotechnics Electric(Jiangsu Electrical Apparatus), 2016(9): 33-37.
[6] 宣耀伟,郑新龙,程斌杰,徐政.海底交流电缆暂态过电压仿真计算[J].高压电器,2014, 50(9):58-65.
XUAN Yaowei, ZHENG Xinlong, CHENG Binjie, XU Zheng. Calculation of transient overvoltage in AC submarine cable system[J]. High Voltage Apparatus, 2014, 50(9): 58-65.
[7] 高俊国,于平澜,李紫云,张晓虹,刘通,刘智宏.基于有限元法的电缆金属护套感应电压仿真分析[J].高电压技术,2014, 40(3):714-720.
GAO Junguo, YU Pinglan, LI Ziyun, ZHANG Xiaohong, LIU Tong, LIU Zhihong. Simulation analysis of induced voltage on metal sheath of power cable based on finite element method[J]. High Voltage Engineering, 2014, 40(3): 714-720.
[8] 郭兴军,牛海清,王晓兵,刘毅刚,蚁泽沛,张尧.高压单芯电缆护套操作过电压计算及冲击试验[J].高电压技术,2007, 33(10):147-150.
GUO Xingjun, NIU Haiqing, WANG Xiaobing, LIU Yigang, YI Zepei, ZHANG Yao. Calculation and test of sheath overvoltage of single-core cable[J]. High Voltage Engineering, 2007, 33(10): 147-150.
[9] 牛海清,王晓兵,刘毅刚,蚁泽沛,张尧.高压单芯电缆金属护套雷电过电压仿真和参数分析[J].高电压技术,2009, 35(4):784-789.
NIU Haiqing, WANG Xiaobing, LIU Yigang, YI Zepei, ZHANG Yao. Simulation and parameter analysis of sheath lightning overvoltage of single-core cable[J]. High Voltage Engineering, 2009, 35(4): 784-789.
[10] MARTI L. Simulation of transients in underground cables with frequency-dependent modal transformationmatrices[J]. IEEE Transactions on Power Delivery, 1988, 3(3): 1099-1110.
[11] 解广润.电力系统过电压[M].北京:水利电力出版社,1985.
[12] 聂晓龙.永磁式真空断路器相控开断技术[D].天津:河北工业大学,2015.
[13] 杨庆,张照辉,席世友,司马文霞,邹密,陈勇.相控断路器投切10kV并联电容器的应用[J].高电压技术,2016, 13(6):1739-1745.

备注/Memo

备注/Memo:
收稿日期:2018-09-30 作者简介:刘宇豪(1995—),男,硕士,主要从事电气系统过电压及其防护研究。 基金项目:中国南方电网有限责任公司重点科技项目(编号:ZBKJXM20170089)。
更新日期/Last Update: 2020-07-07