[1]李茹勤,乔振朋,郭 果,等.特高压南阳站110 kV并联电容器补偿装置管母支撑绝缘子受力及风荷载研究[J].电瓷避雷器,2020,(02):256-260.[doi:10.16188/j.isa.1003-8337.2020.02.040]
 LI Ruqin,QIAO Zhenpeng,GUO Guo,et al.Study on Force and Wind Load of Post Insulator for 110 kV Shunt Capacitor Compensator in UHV Nanyang Station[J].,2020,(02):256-260.[doi:10.16188/j.isa.1003-8337.2020.02.040]
点击复制

特高压南阳站110 kV并联电容器补偿装置管母支撑绝缘子受力及风荷载研究()
分享到:

《电瓷避雷器》[ISSN:1006-6977/CN:61-1281/TN]

卷:
期数:
2020年02期
页码:
256-260
栏目:
绝缘子
出版日期:
2020-04-25

文章信息/Info

Title:
Study on Force and Wind Load of Post Insulator for 110 kV Shunt Capacitor Compensator in UHV Nanyang Station
作者:
李茹勤 乔振朋 郭 果 刘 涛
(国网河南省电力公司检修公司, 郑州 450007)
Author(s):
LI Ruqin QIAO Zhenpeng GUO Guo LIU Tao
(State Grid Henan Electric Power Corporation Maintenance Company, Zhengzhou 450007, China)
关键词:
特高压 并联电容器 支撑绝缘子 受力及风荷载
Keywords:
UHV shunt capacitor post insulators force and wind load
DOI:
10.16188/j.isa.1003-8337.2020.02.040
摘要:
对1 000 kV特高压南阳站110 kV并联电容器补偿装置管母支撑绝缘子进行了受力及风荷载仿真分析,得出在支撑绝缘子等部件结构完好的条件下,在正常运行过程中,绝缘子不会发生破坏,仅当端部受到大于400 kg以上的集中载荷作用时,绝缘子才可能发生破坏的结论。为特高压工程的建设提供参考。
Abstract:
This paper analyzed the force and wind load simulation of 110 kV shunt capacitor compensation device tube post insulator at 1 000 kV UHV Nanyang Station. The conclusion is that if the components of the post insulator are in good condition, insulators will not be damaged during the normal operation; and only when the ends are subjected to concentrated loads greater than 400 kg, the insulators will be destroyed. Provide reference for the construction of UHV project.

参考文献/References:

[1] 耿超,徐楠,李宁.基于有限元的35 kV气体绝缘母线放电机理及改进方案研究[J].四川电力技术,2018, 41(01):49-52.GENG Chao, XU Nan, LI Ning. XU nan LI Ning.research on the mechanism of partial discharge in 35 kV GIL and improvement scheme based on finite element modeling[J]. Sichuan Electric Power Technology, 2018, 41(01): 49-52.
[2] 张月华,刘成柱,吴玉坤,等.±1100 kV特高压干式平波电抗器支撑结构研究[J].变压器,2015(6):27-32.ZHANG Yuehua, LIU Chengzhu, WU Yukun, et al. Research on support structure of±1 100 kV UHV dry-type smoothing reactor[J]. Transformer, 2015(6): 27-32.
[3] 朱赛伟. 特高压绝缘子串在风荷载作用下力学特性的研究[D].中国电力科学研究院,2017.
[4] 王志惠,路蔚旭,何喜梅,等.750 kV GIS设备支撑绝缘子故障分析[J].青海电力,2016, 35(3):56-60.WANG Zhihui, LU Weixu, HE Ximei, et al. Analysis on the fault of the supporting isolator for 750 kV GIS Equipment[J]. Qinghai Electric Power, 2016, 35(3): 56-60.
[5] 马径坦,赵军平,游浩洋,等.GIS支撑绝缘子表面状况对其雷电冲击闪络特性的影响[J].高压电器,2016, 52(4):63-69.MA Jingtan, ZHAO Junping, YOU Haoyang, et al. Influence of surface conditions on flashover characteristics of supporting insulators in GIS under lightning impulse[J]. High Voltage Apparatus, 2016, 52(4): 63-69.
[6] 吴德贯,彭翔,李红元,等.一起500 kV GIL绝缘子炸裂故障分析[J].电瓷避雷器,2016(1):40-43.WU Deguan, PENG Xiang, LI Hongyuan, et al. Analysis of a 500 kV GIL insulator burst fault[J]. Insulators and Surge Arresters, 2016(1): 40-43.
[7] 陈文强,王志惠,刘高飞,等.GIS母线支撑绝缘子断裂原因分析[J].青海电力,2015, 34(3):51-53.CHEN Wenqiang, WANG Zhihui, LIU Gaofei, et al. Analysis on the breakage of the gis bus support insulator[J]. Qinghai Electric Power, 2015, 34(3): 51-53.
[8] 鲁加明,周振华,曹伟伟.GIL用三柱式支撑绝缘子结构研究[J].机械设计与制造,2015(9):52-55.LU Jiaming, ZHOU Zhenhua, CAO Weiwei. The structure study of three colums support insulator with GIL[J]. Machinery Design & Manufacture, 2015(9): 52-55.
[9] 梁炜,杨鹤,曾东.带电安装防风偏支撑绝缘子的专用夹钳设计及应用[J].浙江电力,2013, 32(8):81-84.LIANG Hui, YANG He, ZENG Dong. Design and application of special clamps for live installation of anti-wind deflection supporting insulators[J]. Zhejiang Electric Power, 2013, 32(8): 81-84.
[10] 郭铁桥,郭涛涛,王达达,等.二次射线照相法计算支撑绝缘子缺陷尺寸[J].无损检测,2013, 35(5):78-80.GUO Tieqiao, GUO Taotao, WANG Dada, et al. Calculation of the defect size of support insulator defects size by secondary radiography[J]. Non-Destructive Testing, 2013, 35(5): 78-80.
[11] 隋彬,孙继星,吴广宁,等.间歇性列车风对支撑绝缘子污闪影响分析[J].电瓷避雷器,2012(2):1-5.SUI Bin, SUN Jixing, WU Guangning, et al. Analysis on the influence of intermittent high speed train wind on supporting insulator pollution flashover[J]. Insulators and Surge Arresters, 2012(2): 1-5.
[12] 卢明,胡文,李黎,等.交流500 kV复合绝缘子芯棒断裂原因分析[J].电瓷避雷器,2015(3):23-28.LU Ming, HU Wen, LI Li, et al. Analysis on the causes of the core rod fracture of 500 kV AC composite insulator[J]. Insulators and Surge Arresters, 2015(3): 23-28.
[13] 陈琳依,帅勇,胡加瑞,等.高压支柱瓷绝缘子断裂分析[J].高压电器,2015, 51(7):69-73.CHEN Linyi, SHUAI Yong, HU Jiarui, et al. Fracture analysis of high voltage post porcelain insulators[J]. High Voltage Apparatus, 2015, 51(7): 69-73.
[14] 孙岗,吴光亚,张锐,等.特高压GIS出线套管用空心复合绝缘子运行性能分析[J].电瓷避雷器,2014(6):1-7.SUN Gang, WU Guangya, ZHANG Rui, et al.Analysis on service performance of hollow composite insulators used on UHV GIS bushing [J]. Insulators and Surge Arresters, 2014(6): 1-7.
[15] 曹国旭.绝缘子支柱的恢复力特性试验研究及分析[D].西安:西安建筑科技大学,2008.
[16] 吴光亚,张予,刘建坤,等.1 000 kV特高压绝缘子运行特性研究方向[J].电瓷避雷器,2008(5):11-14.WU Guangya, ZHANG Yu, LIU Jiankun, et al.Study course on service performance of 1 000 kV UHV insulator [J]. Insulators and Surge Arresters, 2008(5): 11-14.

备注/Memo

备注/Memo:
收稿日期:2018-07-19作者简介:李茹勤(1980—),男,本科,工程师,主要从事特高压变电运维检修方面的研究。
更新日期/Last Update: 2020-04-25