10 kV一母多馈电缆线路弧光接地过电压特征分析()
分享到:

《电瓷避雷器》[ISSN:1006-6977/CN:61-1281/TN]

卷:
期数:
2020年02期
页码:
141-147
栏目:
避雷器
出版日期:
2020-04-25

文章信息/Info

Title:
Analysis of Characteristics of Arc Grounding Overvoltage in 10 kV Multiple Feeders
作者:
方春华1 陈 帆1 李 景2 周雨秋1 方 雨1 张 威1
(1.三峡大学电气与新能源学院,湖北 宜昌443002; 2.国网安庆供电公司,安徽 安庆246000)
Author(s):
FANG Chunhua1 CHEN Fan1 LI Jing2 ZHOU Yuqiu1 FANG Yu1 ZHANG Wei1
(1.College of Electrical and New Energy, China Three Gorges University, Yichang 443002, China; 2.State Grid Anqing Electric Power Supply Company, Anqing 246000,China)
关键词:
一母多馈线 小电阻接地 弧光接地 过电压 接地方式
Keywords:
multiple feeders low resistance grounding arc ground overvoltage grounding method
DOI:
10.16188/j.isa.1003-8337.2020.02.023
摘要:
10 kV一母多馈线系统采用小电阻接地方式,当发生弧光接地故障时在故障馈线上会产生较高幅值的过电压,并经母线传递到相邻馈线,从而造成相邻馈线发生击穿跳闸事件。通过PSCAD建立一母多馈线模型,分析了弧光接地过电压对相邻馈线的影响,研究了断路器动作时过电压传递问题,分析了接地方式地对过电压传递的影响。得出了过电压从故障点传递到非故障馈线幅值不断衰减,断路器动作时间小于10 ms能够抑制过电压传递,经消弧线圈接地能够很大程度降低非故障馈线过电压的规律。
Abstract:
10 kV Multiple feeders system adopts a low resistance grounding method. When an arc ground fault occurs, an overvoltage with higher amplitude will be generated on the faulty feeder and transmitted to the adjacent feeder via the bus, which causes a breakdown trip accident. This paper has established the multiple feeders system on the PSCAD platform. By calculating the model, the influence of the arc grounding overvoltage on the adjacent lines is analyzed, the overvoltage transmission when the circuit breaker acts is also studied; and the effect of grounding method on overvoltage is analyzed. It's concluded that the amplitude of the overvoltage from the fault point to the non-faulty feeder is continuously attenuated. A circuit breaker with the operation time less than 10 ms can suppress the transmission of overvoltage in the circuit, and overvoltage of non-fault feeders can be greatly reduced by grounding through arc suppression coil.

参考文献/References:

[1] 张龙钦,李娟,张陵,等.现代配电网单相弧光接地过电压[M].北京:中国电力出版社,2017.
[2] 陈旭.小电流接地系统单相弧光接地故障特性分析及仿真研究[D].北京:华北电力大学,2018.
[3] 韩晓明.冀北地区35 kV及以下系统中性点接地方式的适用性研究[D].北京:华北电力大学(北京),2017.
[4] 高亚栋,杜斌,赵峰,等.中性点经小电阻接地配电网中弧光接地过电压的研究[J].高压电器,2004, 40(5):345-348. GAO Yadong, DU Bin, ZHAO Feng, et al. Study on the arc-grounding overvoltage in the distribution system with neutral point grounded through low-resistance[J]. High Voltage Apparatus, 2004, 40(5): 345-348.
[5] 童奕宾,尤智文,李姝.小电阻接地系统间歇性弧光过电压分析[J].电力系统及其自动化学报,2012, 24(3):116-120. TONG Yibin, YOU Zhiwen, LI Shu. Analysis of intermittent arc overvoltages in low resistance grounded systems[J]. Proceedings of the CSU-EPSA, 2012, 24(3): 116-120.
[6] 余斌,尹项根,朱维钧,等.复合接地消弧方式接地故障分析及保护对策[J].中国电力,2018, 51(12):72-79. YU Bin, YIN Xianggen, ZHU Weijun, et al. Earth fault analysis and protection countermeasures of composite ground arc suppression mode[J]. Electric Power, 2018, 51(12): 72-79.
[7] 张丽萍,邹学东,苏鹏宇,等.配电网弧光接地故障仿真与分析研究[J].智慧电力,2017, 45(12):69-74. ZHANG Liping, ZOU Xuedong, SU Pengyu, et al. Simulation and research analysis of arc-grounding fault in distribution network[J]. Smart Power, 2017, 45(12): 69-74.
[8] 董家读,程志海,郭益辉,等.10 kV系统弧光接地过电压的分析与仿真[J].陕西电力,2012, 40(8):62-65. DONG Jiadou, CHENG Zhihai, GUO Yihui, et al. Anal-ysis and simulation of arc grounding over-voltage in 10 kV system[J]. Shaanxi Electric Power, 2012, 40(8): 62-65.
[9] 黄立新,黄宝富.小电阻接地系统电弧故障试验及其系统级参数优化仿真[J].电瓷避雷器,2012(6):107-110. HUANG Lixin, HUANG Baofu. Experiment andsystem-Level parameters optimization of arc fault in 10 kV low-resistance grounding system[J]. Insulators and Surge Arresters, 2012(6): 107-110.
[10] 陈旭,梁策,刘美岑,等.不对称电网单相弧光接地过电压理论的研究[J].电测与仪表,2018, 55(8):1-6. CHEN Xu, LIANG Ce, LIU Meicen, et al. Study on the theory of overvoltage of single-phase arc grounding faultin asymmetrical power system[J]. ElectricalMeasurement & Instrumentation, 2018, 55(08): 1-6.
[11] 关宇航,李娟,秦艳辉,等.基于ADPSS的配电网弧光接地故障仿真建模[J].电力电容器与无功补偿,2016, 37(6):119-124. GUAN Yuhang, LI Juan, QIN Yanhui, et al. Simulation modeling of arc grounding fault in distribtion network based on ADPSS[J]. Power Capacitor & Reactive Power Compensation, 2016, 37(6): 119-124.
[12] 王德明.Z型接地变原理分析及PSCAD_EMDTC中的建模仿真[J].电气技术,2016(10):46-48. WANG Deming. Principle analysis of Z-type transformer and modeling in PSCAD EMDTC[J]. Electrical Engineering, 2016(10): 46-48.
[13] 许晔,郭谋发,陈彬,等.配电网单相接地电弧建模及仿真分析研究[J].电力系统保护与控制,2015, 43(7):57-64. XU Ye, GUO Moufa, CHEN Bin, et al.Modeling and simulation analysis of arc in distribution network[J]. Power System Protection and Control, 2015, 43(7): 57-64.
[14] 王倩,谭王景,叶赞,等.基于ATP-EMTP的电弧接地故障的建模及仿真[J].电网与清洁能源,2015, 31(1):16-21. WANG Qian, TAN Wangjing, YE Zan, et al. Modeling and simulating of arc grounding fault based on ATP-EMTP[J]. Advances of Power System & Hydroelectric Engineering, 2015, 31(1): 16-21.
[15] 周武仲.电气设备运行技术基础[M].北京:中国电力出版社,2016.
[16] 吕军,陈维江,齐波,等.10 kV配电网经高阻接地方式下过电压及接地故障选线[J].高电压技术,2009, 35(11):2728-2734. LV Jun, CHEN Weijiang, QI Bo, et al. Overvoltage and feeder detection for earth fault underhigh-resistance grounding mode in 10 kV distribution networks[J]. High Voltage Engineering, 2009, 35(11): 2728-2734.
[17] 张赛鸷.高电压技术[M].北京:中国电力出版社,2019.
[18] 刘明岩.配电网中性点接地方式的选择[J].电网技术,2004, 28(16):86-89. LIU Mingyan. Selection of neutral grounding modes in power distribution network[J]. Power System Technology, 2004, 28(16): 86-89.
[19] 刘宝贵.发电厂变电所电气部分第3版[M].北京:中国电力出版社,2016.

备注/Memo

备注/Memo:
收稿日期:2019-04-23作者简介:方春华(1980—),男,博士,副教授,硕导,主要从事高电压绝缘与在线监测技术方面的研究工作。
更新日期/Last Update: 2020-04-25